Viessmann Boiler: Cleaning the burners (fan, venturi and burner tube)
Cleaning the burners (fan, venturi and burner tube) on a Viessmann boiler: Clean the burner fan and burner tube. Close the central gas shut-off valve before any work.
Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0
How to fix cleaning the burners (fan, venturi and burner tube): step by step
- Close the central gas shut-off valve.
- Disconnect the venturi mixing tube from the fan.
- Detach the venturi mixing tube with the combination gas valve and gas connector pipe. Detach connector pipes if fitted.
- Detach the connector from the fan and dismantle the fan.
- Clean the fan housing and fan impeller with compressed air.
- Vacuum the burner tube from inside and out if needed.
- Reassemble in reverse order. Make sure the gasket between fan housing and burner plate is positioned correctly; replace it if damaged.
- Check for gas leakage at the screws and at the gasket between fan housing and burner plate.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 73. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.