Viessmann Boiler: Clean the DHW storage tank
Clean the DHW storage tank on a Viessmann boiler: Visual inspection and cleaning must be done no later than two years after commissioning and then as needed. Do not use hydrochloric acid based cleaners. Use only plastic cleaning tools inside the tank.
Applies to: DHW storage tank
Common causes of clean the dhw storage tank
- Loose deposits inside the DHW tank
- Hard deposits that a high pressure cleaner cannot remove
How to fix clean the dhw storage tank: step by step
- Drain the DHW storage tank.
- Remove insulation A.
- Disconnect the DHW piping from the pipework to stop contamination entering the system.
- Remove the tank clean-out cover B.
- Remove loose deposits with a high pressure cleaner.
- Use a chemical cleaner for hard deposits. Never use hydrochloric acid based agents.
- Flush the DHW tank thoroughly.
- Refit in reverse order.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 222-F B2TB 19, 35, 68, 125 Service Instructions, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.