Viessmann Boiler: Clean the condensate drain system, siphon and neutralizer

Updated · by Aurora Star Tech Inc.

Clean the condensate drain system, siphon and neutralizer on a Viessmann boiler: Annual cleaning of the condensate drain system, which includes the flue collector, siphon, neutralizing system and hoses in between. Water must drain without back pressure.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CU3A 26 to 199

Common causes of clean the condensate drain system, siphon and neutralizer

  • Debris or sediment in the condensate drain or siphon
  • Neutralizer granulate used up or condensate pH below 6.5

How to fix clean the condensate drain system, siphon and neutralizer: step by step

  1. Check that the condensate drain and neutralizer are not blocked and do not leak.
  2. Add water to the combustion chamber and confirm it drains freely. Clean the drain again if there is back pressure.
  3. Undo fitting A on siphon B and remove the siphon from the boiler.
  4. Brush out inlet connector D.
  5. Remove bottom part C of the siphon, clean it and refit it.
  6. Fill the siphon with water before refitting it to inlet connector D. An unfilled siphon allows flue gas to escape.
  7. Clean inside the condensate drain system and the neutralizer (if installed).
  8. Measure condensate pH with a pH strip (field supplied). If pH is below 6.5, replace the granulate.
  9. If contaminated, rinse the neutralization unit with tap water.
  10. Add granulate up to the marked level.
  11. Disconnect the drain hose to the building drain from siphon B and reconnect the neutralizer to siphon B.
  12. Granulate is used up as it neutralizes the condensate. Check the neutralizer manual for minimum level.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 25. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.