Viessmann Boiler: Clean the combustion chamber and heat exchanger

Updated · by Aurora Star Tech Inc.

Clean the combustion chamber and heat exchanger on a Viessmann boiler: Periodic cleaning of the combustion chamber and heating surfaces after the burner is removed. Use only non-metallic tools and a cleaner that is safe for the heat exchanger and refractory.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CU3A 26 to 199

How to fix clean the combustion chamber and heat exchanger: step by step

  1. Perform a gas leak test when the job is finished.
  2. Follow the cleaning agent maker's safety instructions and wear proper protective gear.
  3. Do not use a metal wire brush or powered wire brushes.
  4. Remove the burner assembly (see burner removal on p. 22).
  5. Vacuum loose debris out of the combustion chamber.
  6. Rinse embedded sediment off the heat exchanger with water or a solvent-free cleaner such as a citric acid based product. Keep water off the refractory.
  7. Discoloration of the heat exchanger is normal and does not affect function or service life.
  8. If needed, brush gently with a non-metallic brush to loosen embedded sediment.
  9. Flush the combustion chamber with water until it runs clear through the condensate trap.
  10. Empty and clean any debris from the condensate trap, then reinstall it (see p. 25).
  11. Refit the burner and tighten the nuts diagonally to 3 lb.ft (4 Nm).
  12. Fit the gas supply pipe with a new gasket and tighten to 11 lb.ft (15 Nm).
  13. Plug in the air intake adaptor.
  14. Reconnect the electrical leads to their components.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair