Viessmann Boiler: Choose an outdoor reset heating curve
Choose an outdoor reset heating curve on a Viessmann boiler: Pick one of 9 heating curves so the supply temperature matches the outdoor temperature. Use the offset to fine-tune the room temperature.
Applies to: Vitotron 100 VLN2 outdoor reset
How to fix choose an outdoor reset heating curve: step by step
- Find the design outdoor temperature on the horizontal axis (0 to 70 °F).
- Follow that point up to the desired supply temperature on the vertical axis.
- Choose the curve that crosses at that point. If there is no exact match, choose the closest curve.
- Check the choice periodically and change curves if needed.
- If the room is too cold or too warm across a wide outdoor range, shift the curve with the offset (-9 °F to +9 °F). Shift down if too warm, up if too cold.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
VLN2 04VLN2 06VLN2 08VLN2 12VLN2 14.4
Source: Vitotron 100 VLN2 installation and service instructions, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.