Viessmann Boiler: Checking the mixing valve motor rotation direction
Checking the mixing valve motor rotation direction on a Viessmann boiler: After power-up the boiler runs a self-test that opens and closes the mixing valve. The supply temperature sensor should read a higher temperature when the valve opens. If the temperature drops, the motor turns the wrong way or the valve set is fitted incorrectly.
Applies to: Vitodens 222-F B2TB extension kit
Common causes of checking the mixing valve motor rotation direction
- Motor turning in the wrong direction
- Mixing valve set incorrectly fitted
How to fix checking the mixing valve motor rotation direction: step by step
- Let the boiler complete its self-test.
- Set the mixing valve manually to Open.
- Check that the supply temperature sensor reads a higher temperature.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Vitodens 222-F B2TB service instructions, p. 87. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.