Viessmann Boiler: Checking the flue gas temperature sensor
Checking the flue gas temperature sensor on a Viessmann boiler: The flue gas temperature sensor locks out the boiler when the permissible flue gas temperature is exceeded. The interlock must be reset after the flue system has cooled down.
Applies to: Vitocrossal 300 CU3A 26 to 199
Common causes of checking the flue gas temperature sensor
- Flue gas temperature above permissible limit
- Faulty flue gas temperature sensor
How to fix checking the flue gas temperature sensor: step by step
- Let the flue system cool down.
- Pull the leads from flue gas temperature sensor A.
- Measure the sensor resistance and compare it with the curve.
- Replace the sensor if the deviation is severe.
- Press reset button R to clear the interlock.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 95. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.