Viessmann Boiler: Checking and correcting the rotation direction of the mixing valve motor
Checking and correcting the rotation direction of the mixing valve motor on a Viessmann boiler: The boiler runs a self-test at power-up that opens and closes the mixing valve. If the supply sensor temperature drops when the valve should be opening, the motor is turning the wrong way or the valve set is fitted incorrectly.
Applies to: Extension kit mixing valve motor
Common causes of checking and correcting the rotation direction of the mixing valve motor
- Motor turning in the wrong direction
- Mixing valve set incorrectly fitted
How to fix checking and correcting the rotation direction of the mixing valve motor: step by step
- Switch on the boiler and let the self-test run.
- During the self-test, set the mixing valve manually to Open.
- Check that the supply temperature sensor reads a higher temperature.
- If the temperature drops, disconnect main power before opening the boiler.
- Remove the upper casing cover of the extension kit.
- At plug gS, swap the cores at terminals in the marked positions.
- Refit the casing cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 97. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.