Viessmann Boiler: Check the room temperature sensor (Part No. 7133 379)
Check the room temperature sensor (Part No. 7133 379) on a Viessmann boiler: Test the room sensor resistance and compare it with the room temperature shown on the control.
Applies to: Room temperature sensor, Part No. 7133 379
How to fix check the room temperature sensor (part no. 7133 379): step by step
- Disconnect the wires from the sensor.
- Measure the sensor resistance at terminals 9 and 13b.
- Compare the reading with the resistance table for the room temperature.
- Compare the resistance-based temperature with the actual room temperature shown on the display (scan on page 109).
- Check the installation first. Replace the sensor if the deviation is severe.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Source: Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 152. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.