Viessmann Boiler: Check the return temperature sensor (strap-on or immersion)
Check the return temperature sensor (strap-on or immersion) on a Viessmann boiler: The return sensor plugs into socket 17A or 17B on the control unit. Check it by resistance against the current return temperature.
Applies to: Return temperature sensor T2 / T1
Common causes of check the return temperature sensor (strap-on or immersion)
- Sensor reading differs significantly from actual temperature
How to fix check the return temperature sensor (strap-on or immersion): step by step
- Disconnect plug aJA or aJB in the terminal compartment.
- Measure the sensor resistance between terminals 1 and 2 of the plug.
- Compare the reading with the current temperature using the resistance table.
- If the value differs significantly, check the installation and replace the sensor if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation manual, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.