Viessmann Boiler: Check the outdoor temperature sensor
Check the outdoor temperature sensor on a Viessmann boiler: Check the sensor resistance against the outdoor temperature. Replace the cable or sensor if the readings are far from the curve.
Applies to: Outdoor temperature sensor 7820 148
Common causes of check the outdoor temperature sensor
- Sensor reading differs severely from the curve.
How to fix check the outdoor temperature sensor: step by step
- Remove plug.
- Measure sensor resistance at terminals 1 and 2 of the plug.
- Compare with the table: -10 °C / 14 °F about 480, 0 °C / 32 °F about 500, 20 °C / 68 °F about 546.
- If readings deviate severely, disconnect the cores from the sensor and repeat the measurement; compare with the actual temperature.
- Replace the cable or the outdoor temperature sensor depending on the result.
- Scan the actual temperature.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW2 installation and service instructions, p. 99. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.