Viessmann Boiler: Check neutralization unit
Check neutralization unit on a Viessmann boiler: The granulate is used up as it neutralizes the condensate. The red mark shows the minimum fill level. A field-supplied pH strip is needed.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
Common causes of check neutralization unit
- Condensate pH below 6.5
- Contaminated granulate
How to fix check neutralization unit: step by step
- Check the condensate pH with a pH strip.
- If pH is below 6.5, replace the granulate.
- If the unit is contaminated, rinse it with tap water.
- Add granulate up to the red minimum fill mark.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.