Viessmann Boiler: Check mixing valve extension kit rotation and direction
Check mixing valve extension kit rotation and direction on a Viessmann boiler: The boiler runs a self-test after power-up in which the mixing valve opens and closes again. The flow sensor must read higher when the valve is opened. If the temperature drops, the motor is turning the wrong way or the valve set is fitted incorrectly.
Applies to: Extension kit for heating circuit with mixing valve
Common causes of check mixing valve extension kit rotation and direction
- Motor turning in wrong direction
- Mixing valve set incorrectly fitted
How to fix check mixing valve extension kit rotation and direction: step by step
- After the self-test, set the mixing valve manually to Open.
- Check that the flow temperature sensor reads a higher temperature.
- If the temperature drops, remove the upper casing cover of the extension kit.
- At plug gS, swap the cores at terminals '|' and '~'.
- Refit the casing cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 85. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.