Viessmann Boiler: Check combustion quality
Check combustion quality on a Viessmann boiler: Measure the CO2 or O2 content of the flue gas, then use the air factor table to find the air factor. The result should fall within λ 1.24 to 1.44.
Applies to: Vitodens 222-F, B2TB 19, 35, 68, 125
How to fix check combustion quality: step by step
- Measure CO2 or O2 in the flue gas.
- Find the matching air factor λ in the air factor table for your gas type (natural gas or liquid propane).
- Confirm λ is between 1.24 and 1.44.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Viessmann Vitodens 222-F B2TB service instructions, p. 34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.