Viessmann Boiler: Check combustion air leakage in the coaxial vent
Check combustion air leakage in the coaxial vent on a Viessmann boiler: Simple leak test on the coaxial air intake gap during start-up.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix check combustion air leakage in the coaxial vent: step by step
- Measure CO2 in the combustion air in the coaxial gap of the air intake pipe using the port on the vent adaptor.
- Pass if CO2 is no higher than 0.2% or O2 is no lower than 20.6%.
- If the readings fail, check the venting system thoroughly.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HB 45, 57, 160, 199 Service Instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.