Updated · by Aurora Star Tech Inc.

Check CO2 and O2 at the boiler vent using the actuator test on a Viessmann boiler: Used at initial start-up and maintenance. The burner is forced to the lower and upper outputs so the flue readings can be checked at each.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CU3A 26 to 199

Common causes of check co2 and o2 at the boiler vent using the actuator test

  • Venting leak
  • Boiler not set for the fuel in use

How to fix check co2 and o2 at the boiler vent using the actuator test: step by step

  1. Connect a flue gas analyzer to test port A on the vent pipe adaptor.
  2. Open the gas shut-off valve, start the boiler and create a heat demand.
  3. Open the service menu (the button combination is not legible in the source text; check the full manual).
  4. Select the Actuator test menu.
  5. Select 'Base load OFF' to run the lower output. The display then shows 'Base load ON'. The manual also says the burner runs at its upper output here, which conflicts with the lower output, so confirm the output at the unit.
  6. Select 'Full load OFF' to run the upper output. The display then shows 'Full load ON'.
  7. Measure CO2 and O2 at the vent pipe adaptor and record them on the Maintenance Record (p. 113).
  8. Select 'Full load ON' and confirm with OK. Measure CO2 and O2 again and record them.
  9. Press OK when done, or exit with the back button.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199

Source: Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 28. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977