Viessmann Boiler: Check CO2 and O2 at low and high fire
Check CO2 and O2 at low and high fire on a Viessmann boiler: Run the boiler in actuator test at low fire and high fire and check the combustion readings at each.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
Common causes of check co2 and o2 at low and high fire
- Combustion readings outside the allowed range
How to fix check co2 and o2 at low and high fire: step by step
- Connect the flue gas analyzer to the test port at the vent pipe adaptor.
- Open the gas shut-off valve, start the boiler and create a heat demand.
- Enter the service menu and select the actuator test.
- For low fire, select Base load OFF so Base load ON appears. Measure CO2 and O2.
- Select 'all actuators off' to end low fire.
- For high fire, select Full load OFF so Full load ON appears. Measure CO2 and O2.
- Exit the actuator test and record both readings on page 101.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 30-31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.