Updated · by Aurora Star Tech Inc.

Check burner motor rotation at commissioning on a Viessmann boiler: Three-phase burner motors can run backwards if the phases are wired wrong. Correct it at the burner terminals, not in the control.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 3 PH 208, 460 or 575 V burners on VD2/VD2A/CT3 controls

How to fix check burner motor rotation at commissioning: step by step

  1. Check motor rotation against the arrow on the burner.
  2. If the rotation is wrong, disconnect power.
  3. Reverse wires BK1 and BK2 on the burner terminals.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More commissioning tips for boiler

Source: Vitotronic 300 GW2 installation and service instructions, p. 54. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.