Viessmann Boiler: Check boiler, DHW tank, flow and low-loss header temperature sensors
Check boiler, DHW tank, flow and low-loss header temperature sensors on a Viessmann boiler: Sensor type is NTC 10 kΩ. Compare measured resistance with the curve (curve not reproduced in this extract). Drain the boiler before replacing the boiler water sensor.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
How to fix check boiler, dhw tank, flow and low-loss header temperature sensors: step by step
- Boiler temperature sensor: remove the lead to the boiler water temperature sensor (§ or §A) and measure resistance.
- DHW tank sensor: pull plug % from the cable harness at the control unit and measure resistance.
- Supply or low-loss header sensor: pull plug X3 from the control unit and measure across terminals X3.4 and X3.5. Only one of these sensors may be used.
- Replace the sensor if the values deviate severely from the curve.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 84. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.