Viessmann Boiler: Check and clean ignition and ionization electrodes
Check and clean ignition and ionization electrodes on a Viessmann boiler: Check electrodes for wear and contamination, clean them and check the gaps.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199
Common causes of check and clean ignition and ionization electrodes
- Wear or contamination on the electrodes
- Electrode gaps not as specified
- Damaged electrodes
How to fix check and clean ignition and ionization electrodes: step by step
- Check the ignition electrodes and ionization electrode for wear and contamination.
- Clean the electrodes with a small brush (not a wire brush) or emery paper.
- Check the electrode gaps. If the gaps are wrong or the electrodes are damaged, replace them and align them with new gaskets.
- Tighten the electrode fixing screws to 1.5 lb.ft (2 Nm) with a calibrated torque wrench.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.