Viessmann Boiler: Check an NTC 10 kΩ sensor (outside, supply, DHW, return)
Check an NTC 10 kΩ sensor (outside, supply, DHW, return) on a Viessmann boiler: Check a Viessmann NTC 10 kΩ sensor against the resistance curve. The temperature-resistance table values are not legible in the extracted text.
Applies to: Outside temperature sensor, supply temperature sensor, DHW tank sensor, return sensor
Common causes of check an ntc 10 kΩ sensor (outside, supply, dhw, return)
- Sensor reading far from the curve
- Damaged lead or wiring
How to fix check an ntc 10 kΩ sensor (outside, supply, dhw, return): step by step
- Pull the corresponding sensor plug.
- Measure the sensor resistance across terminals 1 and 2 and compare it with the curve.
- If the reading is far off, disconnect the wires from the sensor and repeat the test on the sensor alone.
- Replace the lead if the sensor is good; replace the sensor if it is still off.
- Check the installation if the deviation is severe before replacing the sensor.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
Source: Vitotronic 200-H HK1B installation and service instructions, p. 75. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.