Viessmann Boiler: Category I venting requirements (natural gas or propane)

Updated · by Aurora Star Tech Inc.

Category I venting requirements (natural gas or propane) on a Viessmann boiler: Category I venting is the standard option for this boiler on gas. Use Type B or Type L vent for the whole run where possible. B-vent is not allowed on #2 oil.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitorond 200 VD2 Category I (natural gas, liquid propane)

Common causes of category i venting requirements (natural gas or propane)

  • Down draft or condensation in the vent

How to fix category i venting requirements (natural gas or propane): step by step

  1. Use approved vent material only. Do not connect the vent to any mechanical draft system under positive pressure.
  2. Put the boiler as close to the chimney as possible, with the shortest run and fewest elbows. Avoid long horizontal runs.
  3. Support horizontal runs so they do not sag. Give them at least 1/4 in. (6 mm) rise per ft. from the boiler to the terminal. Strap every 4 ft. (1.2 m).
  4. Insulate the vent pipe.
  5. Terminate outside at least 6 ft. (1.8 m) above the boiler. Extend the vent at least 3 ft. (91 cm) above the roof penetration.
  6. Make sure the termination is at least 2 ft. (61 cm) above any building part within 10 ft. (3 m) horizontal and at least 2 ft. (61 cm) above roof peaks within 10 ft. (3 m).
  7. Correct any down draft or condensation problems.
  8. Install a stainless steel liner in masonry or unlined chimneys where recommended.
  9. With B-vent on natural gas or LP, measure stack temperature before dilution air. It must not exceed 480 F (249 C).
  10. Follow local codes.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 23. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.