Viessmann Boiler: Cascade strategy: net calorific 2
Cascade strategy: net calorific 2 on a Viessmann boiler: An extra boiler starts only when all active burners at maximum output cannot reach the set supply temperature. A boiler shuts down when its burner is at minimum output because of a large negative deviation and output is still too high. Gives long burner run times. Net calorific 2 is the only strategy suitable for series arrangements.
Applies to: Vitocontrol-S VD2/CT3/CM2 cascade, series arrangement
How to fix cascade strategy: net calorific 2: step by step
- Start-up: the start-up integral must exceed the limit set in coding 45. The next boiler in the sequence then starts.
- Shutdown: the shutdown integral must exceed the limit set via coding 3d: 1, then the last boiler started is shut down.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 125, 127. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.