Viessmann Boiler: Cascade strategy: net calorific 1 (coding 3C: 1)
Cascade strategy: net calorific 1 (coding 3C: 1) on a Viessmann boiler: Conventional boilers run at their upper output range to prevent condensate from low return temperatures. Fewest boilers are active.
Applies to: Vitocontrol-S VD2/CT3/CM2 cascade
How to fix cascade strategy: net calorific 1 (coding 3c: 1): step by step
- Start-up: the start-up integral must exceed the limit set in coding 45. The next boiler in the sequence then starts.
- Shutdown: a boiler shuts down (coding 3d: 1) when the remaining boilers can meet the required output without the boiler started last.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 127. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.