Viessmann Boiler: Calibrate the burner with combustion analysis
Calibrate the burner with combustion analysis on a Viessmann boiler: Measure at the final site with calibrated equipment and adjust the burner to local conditions.
Applies to: VR1 40 to 63, 161 to 245 with #2 oil
Common causes of calibrate the burner with combustion analysis
- Weather
- Length of horizontal vent pipe
- Chimney diameter and height
- Side wall (power) venting
- Altitude
- Oil quality and heating value
- Other fuel appliances running at the same time
How to fix calibrate the burner with combustion analysis: step by step
- Use calibrated combustion equipment at the final installation site.
- Take CO2, stack temperature, draft and CO readings in the flue pipe between the boiler and the barometric draft regulator, before dilution air.
- Measure overfire draft at the combustion chamber observation port opening.
- Adjust the burner until results are acceptable for the local conditions.
- Refer to the burner technical table on page 41 or 42 of the manual for burner data.
- Refer to the Beckett or Riello burner instructions for burner settings.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 installation and service manual, p. 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.