Updated · by Aurora Star Tech Inc.

Burner reassembly and final combustion check on a Viessmann boiler: Reassembly torques and the required combustion check after burner work.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0

How to fix burner reassembly and final combustion check: step by step

  1. Position the burner plate with burner mesh assembly on the 8 studs on the boiler section. Tighten nuts to 7.3 lb.ft (10 Nm).
  2. Position the upper burner section above the burner plate. Tighten the M10 nuts to 7.3 lb.ft (10 Nm).
  3. Push on the ignition and ionization electrode connectors.
  4. Insert connectors at the plug-in panel and at the burner control unit. Insert the mains plug last.
  5. Fit the gas connection pipe.
  6. Check the fitting for gas tightness. Do not use leak detection spray near electrical contacts.
  7. Start the burner and carry out a function test.
  8. Take a CO2 reading after each burner dismantling, per the items on pp. 67 and 68.
  9. Record the readings in the maintenance record on p. 162.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0

Source: Viessmann Vitocrossal 300 CA3B service instructions, p. 75. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.