Viessmann Boiler: Burner motor power supply, 3 PH 208, 460 or 575 V
Burner motor power supply, 3 PH 208, 460 or 575 V on a Viessmann boiler: For burners with three-phase supply at 208, 460 or 575 V. Fuse and wire sizing come from the burner manual.
Applies to: VD2/VD2A/CT3 controls, 3 PH burners
How to fix burner motor power supply, 3 ph 208, 460 or 575 v: step by step
- Disconnect power to the burner and the boiler control.
- Connect 3-phase power to terminals 21, 22, 23 and 24 on the DIN rail in the connection enclosure.
- Provide a fuseable disconnect according to local codes.
- Connect the supplied power cable to the motor terminals on the burner.
- Connect the cable plug to the socket on the DIN rail in the connection enclosure.
- During commissioning, check motor rotation and reverse BK1 and BK2 at the burner terminals if it turns the wrong way.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW2 installation and service instructions, p. 54. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.