Viessmann Boiler: Boiler temperature control sequence
Boiler temperature control sequence on a Viessmann boiler: The boiler water temperature is controlled by a two-stage or modulating burner. The set point comes from Vitocontrol-S. Three sensors monitor the boiler water: the fixed high limit (110 C, adjustable to 99 C), the adjustable high limit (95 C, adjustable to 87 or 100 C) and the boiler temperature sensor KTS. The electronic maximum limit can be set from 20 to 127 C (68 to 261 F) via coding 06.
Applies to: Vitotronic 100 GC1 boiler temperature control
How to fix boiler temperature control sequence: step by step
- The burner starts when the boiler is 2 C (3.6 F) below the calculated set point.
- The burner may be delayed a few minutes depending on connected auxiliary equipment and fuel type.
- The burner switches off at the switch-off differential set in coding 13.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitocontrol-S VD2/CT3/CM2 installation and service manual, p. 123. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.