Viessmann Boiler: Boiler pump runs continuously after multi-boiler change
Boiler pump runs continuously after multi-boiler change on a Viessmann boiler: When a Vitodens 200 B2HB goes from single to multi-boiler operation, coding address 30:0 can reset to 30:3, which keeps the boiler pump running continuously.
Applies to: Vitodens 200-W B2HB 45, 57, 160, 199 (multi-boiler)
Common causes of boiler pump runs continuously after multi-boiler change
- Coding address 30:0 automatically resets to 30:3 when switching from single boiler to multi-boiler operation
How to fix boiler pump runs continuously after multi-boiler change: step by step
- Check that the coding address for each boiler is 30:0.
- Set it to 30:0 if necessary (see p. 59).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 83. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.