Viessmann Boiler: Boiler location, venting and flue temperature
Boiler location, venting and flue temperature on a Viessmann boiler: The CU3A is a direct vent appliance and can be sealed-combustion in any room size or ventilation type. It can go in living areas, unventilated utility rooms, closets, alcoves and attics with a direct flue outlet, with no clearance needed from combustibles. Follow local and national codes. Concentric PP(s) direct vent systems are certified with the boiler. Single-wall venting (AL29-4C, PP(s) or CPVC, listed for category IV) is also allowed. Max flue gas temperature is 230°F (110°C), so no flue temperature protection is needed. Use the Vitocrossal 300 CU3A venting instructions for details.
Applies to: Vitocrossal 300 CU3A
How to fix boiler location, venting and flue temperature: step by step
- Install as a sealed-combustion direct vent unless using an approved single-wall system.
- Use only a certified concentric or approved single-wall venting system.
- Confirm flue pipe rating is at least 230°F (110°C).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A application guide, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.