Viessmann Boiler: Boiler hydrostatic pressure test
Boiler hydrostatic pressure test on a Viessmann boiler: The boiler must be leak tested and hydrostatically pressure tested before connection to piping or power. Test pressure is between 110 and 120 psig (689 to 827 kPa).
Applies to: Vitorond 200 VD2 boiler before startup
How to fix boiler hydrostatic pressure test: step by step
- Install supply and return headers with pressure gauge, temperature gauge, air vent, low water cut-off, drain valve and bypass pump. Pipe up to isolation valves and close them.
- Install temporary caps on the relief valve and expansion tank nipples.
- Connect a hose to the boiler drain valve and fill slowly until the gauge reads a maximum of 120 psig (827 kPa).
- Hold pressure for 30 minutes and do not leave the boiler unattended.
- Check all push nipples and pipe connections for leaks with a flashlight. Place paper under the cast iron block to catch minor leaks.
- After 30 minutes, open the drain valve slowly to release pressure.
- Remove caps and install the relief valve and expansion tank right away.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 installation manual, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.