Viessmann Boiler: Boiler control is not active (green power LED off)
Boiler control is not active (green power LED off) on a Viessmann boiler: The control shows no power indication.
Applies to: Vitotronic 100 KW10B
Common causes of boiler control is not active (green power led off)
- Power switch is in the off position
- Main power to the control and heating system is not on
- Fuse on the Vitotronic control has blown
How to fix boiler control is not active (green power led off): step by step
- Set the power switch to the on position.
- Turn on the main power and confirm 120 VAC is supplied to the control receptacle.
- If the fuse has blown, replace it with the same type and rating: F1, T 6.3 A / 250 V, slow blow.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100 KW10B operating manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.