Viessmann Boiler: Boiler control housing installation
Boiler control housing installation on a Viessmann boiler: Mount the control housing on the side panel and route capillaries and the boiler sensor away from heat sources. Electrical connections are covered in the boiler control instructions.
Applies to: Vitorond 200 VD2 boiler control housing
How to fix boiler control housing installation: step by step
- Drill four 3 mm holes in side panels A and B as shown. Use a mirror image for left-side mounting.
- Punch a 22 mm (7/8 in.) opening in the side panel.
- Install the control harness bracket with supplied 8-32 self-tapping screws.
- Install the burner harness bracket with the two supplied screws.
- Install the top mounting hole cover with two supplied self-tapping screws.
- Remove the two plugs on the back of the control housing with a flathead screwdriver, then mount the housing on the side panel.
- Secure the control housing with the two supplied screws.
- Run the capillaries and boiler temperature sensor through the 22 mm opening and push them as far as possible into the sensor well.
- Keep cabling and capillaries away from high heat sources such as the vent, chimney or supply/return piping.
- Follow the boiler control installation instructions for electrical connections.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 installation manual, p. 31-32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.