Viessmann Boiler: Bleed air from the boiler heat exchanger
Bleed air from the boiler heat exchanger on a Viessmann boiler: Vent the heat exchanger on the boiler side. Do not use the heating side pressure relief valve for this, as it can damage the equipment.
Applies to: Vitodens 222-F B2TB 19, 35, 68, 125
How to fix bleed air from the boiler heat exchanger: step by step
- Close the field supplied shut-off valves on the heating water side.
- Remove cover panel A.
- Connect the supplied drain hose to heat exchanger air vent valve B and route the other end to the drain.
- Open air vent valve B with the supplied key.
- Fill through sediment faucet C in the heating return and vent using mains pressure until no more air noise is heard.
- Close valve B and fill valve C, then open the heating water shut-off valves.
- Start the venting program from the service menu and end it with OK or the arrow key.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
Source: Viessmann Vitodens 222-F B2TB service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.