Viessmann Boiler: Application 4: ZC1 setpoint demand with ZC2 weather compensated

Updated · by Aurora Star Tech Inc.

Application 4: ZC1 setpoint demand with ZC2 weather compensated on a Viessmann boiler: ZC1 is a low-temperature on/off circuit with an outdoor reset curve during a thermostat call. ZC2 (air handler) runs a fixed setpoint. A thermostatic mixing valve is needed to protect ZC1 when the air handler is running. ZC1 uses pump output 28/20. The ZC2 call starts the 157 plug pump.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Application 4 (CU3I 2ZC2ZP.01)

How to fix application 4: zc1 setpoint demand with zc2 weather compensated: step by step

  1. Select the number of zone circuit connections to match the thermostats on the DE connections, then press OK.
  2. Select Weather Compensated for ZC1 and press OK.
  3. Confirm the ZC1 settings and press OK. These can be changed later.
  4. Assign the ZC1 pump as the 28/20 output.
  5. Set ZC2 to Fixed Setpoint and press OK.
  6. Enter the ZC2 zone target temperature.
  7. For ZC2 pump, select the 157 Output. If the air handler controls the pump, select No Output.
  8. Review the output summary and finish start-up.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199

Source: Vitocrossal 300 CU3A Application Guide, p. 32. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.