Viessmann Boiler: Application 4: wiring and piping notes for air handler and radiant loop
Application 4: wiring and piping notes for air handler and radiant loop on a Viessmann boiler: Application CU3I 2ZC2ZP.01. The CU3A is a high-mass boiler, so primary/secondary piping is not required. A thermostatic mixing valve protects the radiant floor from excessive hot water. Heat demand from the air handler must be a dry (potential-free) contact.
Applies to: Application 4 (CU3I 2ZC2ZP.01)
How to fix application 4: wiring and piping notes for air handler and radiant loop: step by step
- Wire the air handler heat demand as a dry, potential-free contact.
- Wire the radiant circuit call as a dry contact from a thermostat, zone valve or multi-zone controller.
- Install the jumper between the 40A plug and the 157 plug.
- If P4 is controlled by the air handler, do not wire a pump.
- Use the pressure drop and pump sizing chart for the CU3A 94/125 or 160/199 model as applicable.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A Application Guide, p. 30-31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.