Viessmann Boiler: Application 4: two heat circuits, ZC1 low-temperature and air handler on HC2

Updated · by Aurora Star Tech Inc.

Application 4: two heat circuits, ZC1 low-temperature and air handler on HC2 on a Viessmann boiler: Two circuits at different temperatures. ZC1 is a low-temperature circuit and the air handler is a mid/high-temperature circuit. A thermostatic mixing valve must protect ZC1 from high water temperature when the air handler runs. The air handler controls the P3 circulator in heat circuit 2 and its heat demand must be a dry contact. The radiant circuit dry contact can come from a thermostat, zone valve or multi-zone controller. Hydraulically separate the boiler and system loops with closely spaced tees or a low-loss header.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Application code VD2T 2HC2T2ZP.01 (Application 4, pages 38-39, 42-44)

How to fix application 4: two heat circuits, zc1 low-temperature and air handler on hc2: step by step

  1. Wire the outdoor sensor and the low-loss header sensor as shown.
  2. Wire the air handler heat demand as a potential-free dry contact.
  3. Wire the infloor heat control dry contact to the radiant circuit.
  4. Fit a thermostatic mixing valve to protect ZC1 when the air handler is running.
  5. Confirm the P1 boiler circulator is used; it is built into the boiler.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125

Source: Viessmann Vitodens 222-F B2TB application guide, p. 38-40, 42-43. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.