Viessmann Boiler: Annual heating contractor service checklist

Updated · by Aurora Star Tech Inc.

Annual heating contractor service checklist on a Viessmann boiler: Annual service must be done by qualified personnel. Correct any deficiencies right away.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitorond 200 VD2A boilers

How to fix annual heating contractor service checklist: step by step

  1. Test safety high limits by lowering settings and switching the burner on and off.
  2. Test burner and accessories against their maintenance checklist.
  3. Test and establish proper system water chemistry.
  4. Check flue pipe, chimney connection and chimney.
  5. Check the pressure relief valve, system pressure and automatic feed if fitted.
  6. Check heating pipe joints, valves and air vents for leaks and correct any leaks at once.
  7. Check combustion air and ventilation to the boiler room.
  8. Check for combustibles or chemicals stored near the boiler.
  9. Test the low water cut-off and confirm it works per the manufacturer.
  10. Check oil-tight fuel lines and replace or clean fuel filters annually.
  11. Check and inspect the oil tank.
  12. Check gas-tight connections on gas piping, unions, gas valve and manifold.
  13. Check proper ignition on oil or gas operation.
  14. Have a qualified technician perform the combustion test.
  15. Test the door safety switch.
  16. Check the low- and/or high-pressure gas switch if fitted.
  17. Inspect the main burner flame.
  18. Check the circulating pump lubrication or maintenance if field-installed.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitorond 200 VD2A service instructions, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977