Viessmann Boiler: Adjust the fixed high limit to 99°C / 210°F

Updated · by Aurora Star Tech Inc.

Adjust the fixed high limit to 99°C / 210°F on a Viessmann boiler: The fixed high limit leaves the factory at 110°C / 230°F. It is required to be set to 99°C / 210°F for the Vitocrossal 300. Once set to 99°C / 210°F it cannot be reset to 110°C / 230°F. If set to 99°C / 210°F, do not set the adjustable high limit above 75°C / 167°F.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 and condensing boilers as listed in the limit table

How to fix adjust the fixed high limit to 99°c / 210°f: step by step

  1. Disconnect power to the control and the burner.
  2. Unclip the fuse box and swing it upwards.
  3. Turn the slotted screw on the rear of the fixed high limit until the slot points to 99°C / 210°F.
  4. Refit the fuse box.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitotronic 300 GW2 installation and service instructions, p. 23. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.