Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Adjust the adjustable high limit to 100°C

Updated · by Aurora Star Tech Inc.

Adjust the adjustable high limit to 100°C on a Viessmann boiler: Field change of the adjustable high limit from the factory 95°C to 100°C.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 100 GC1 adjustable high limit

How to fix adjust the adjustable high limit to 100°c: step by step

  1. Disconnect power to the control and the burner.
  2. Lever out and remove the selector knob R behind the hinged cover, using a suitable screwdriver.
  3. Break off the marked cams on the stop dial with pointed pliers, as shown in the figure.
  4. Refit selector knob R so the marking sits in the centre of the selected range.
  5. Confirm coding address 06 is set as required.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitotronic 100, type GC1

Source: Viessmann Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 40. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977