Service & test modes: Boiler tips (part 3 of 10)
Short, practical technician tips on service & test modes for boiler. Check each one against the manual for your exact model before acting.
Brief scan of temperatures and components
Viessmann · Vitodens 200-W diagnosis
Shows temperatures, software versions and connected components on 9 lines with 6 fields each.
- Press OK and the second button shown in the manual together for about 4 seconds.
- Select "Diagnosis".
- Select "Brief scan".
- Press OK.
Brief scan of temperatures, versions and components
Viessmann · Vitodens 200-W B2HA 45, 60
Shows 9 lines with 6 fields each: temperatures, software versions and connected components.
- Enter the service level.
- Select Diagnosis.
- Select Brief scan.
- Press OK. The display shows 9 lines of 6 fields.
Bring back an acknowledged fault
Viessmann · Vitotronic 200 KW2
Lets you look again at a fault that was already acknowledged.
- Hold the scan button for about 3 seconds.
- Select the acknowledged fault with the arrow buttons.
- Read the fault shown on the display.
Burner fault codes
Viessmann · Vitocrossal 300 CA3B
Burner faults show on the control unit display. The manual sends burner fault details to the burner section of the service instructions, which is not in these pages.
- Use the burner section of the service instructions for burner-side fault work.
Call up and change Coding 1
Viessmann · Vitotronic 100 GC1, Coding 1
Enter Coding 1 on the Vitotronic 100 control to view or change coding addresses.
- Press the 9 and w keys together for about two seconds, until the first arrow appears in the display.
- Select the coding address with the arrow keys. The address flashes. Confirm to see the value flash.
- Change the value with the arrow keys and confirm. The value stays steady for about 2 seconds, then the display flashes again.
- Select further addresses with the arrow keys if needed.
- Press the 9 and w keys together for about one second to exit.
Call up and change Coding 2
Viessmann · Vitotronic 100 GC1, Coding 2
Enter Coding 2 on the Vitotronic 100 control to view or change coding addresses.
- Press the w and rw keys together for about two seconds, until the first two arrows appear in the display. Confirm.
- Select the coding address with the arrow keys. The address flashes. Confirm to see the value flash.
- Change the value with the arrow keys and confirm. The value is saved and stays steady for about 2 seconds, then the display flashes again.
- Select further addresses with the arrow keys if needed.
- Press the w and rw keys together for about one second to exit.
Call up coding level 1
Viessmann · Vitodens 200-W B2HA 45, 60
Coding level 1 groups codes by General, Boiler, DHW, Solar, Heating circuit 1/2/3 and All codes std device.
- Press OK and the second key together for about 4 seconds.
- Select Coding level 1.
- Select the group of the code you need.
- Select the coding address.
- Choose the value from the table and confirm with OK.
- To reset all codes to factory setting, select Standard setting in Coding level 1 (this also resets level 2 codes).
Call up fault memory
Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
The ten most recent faults are stored. The list scrolls from the newest to the oldest. The display closes automatically after 20 seconds with no key press. A non-lockout fault with no code may still show its cause here.
- Hold the S button for more than 2 seconds until the indicator flashes.
- Press Y until "4" shows under Service.
- Press S. "4" shows under Status.
- Press Y or B to choose: 1 = display fault codes, 2 = detail fault codes, 3 = clear fault memory.
- Press S to open the selected view.
- Press Y or B to scroll through the fault codes.
Call up the commissioning assistant later
Viessmann · Vitodens 100-W B1HE/B1KE
Use this to finish commissioning after the boiler has already been switched on.
- Press the two buttons shown on the control panel together with OK for about 4 seconds, then release.
- Select Basic settings and press OK.
- Select Commissioning assistant and press OK.
Calling up and changing coding 1
Viessmann · Vitotronic 300-K, MW1S
Coding 1 is opened with the 9 and w buttons. Each address and value is confirmed one at a time.
- Press 9 and w together for about 2 seconds.
- Select the address with the up or down button; confirm to make the value flash.
- Change the value with the up or down button and confirm.
- The display briefly shows Adopted and the address flashes again.
- Select further addresses as needed.
- Press 9 and w together for about 1 second to exit.
Calling up and changing coding 2
Viessmann · Vitotronic 300-K, MW1S
Coding 2 is opened with the w and rw buttons. Addresses are scrolled in the order shown in the address map.
- Press w and rw together for about 2 seconds and confirm.
- Select the address with the up or down button; confirm to make the value flash.
- Change the value with the up or down button and confirm.
- The display briefly shows adopted and the address flashes again.
- Select further addresses as needed.
- Press w and rw together for about 1 second to exit.
Change altitude setting on burner control
Viessmann · Vitocrossal 200 CM2 burner control
Set the burner for low or high altitude. The burner must be in standby (Status 0, Service 0).
- Press button S and hold for more than 2 seconds until the display area flashes.
- Press button Y or E until 6 appears in the Service display.
- Press button S until 6 appears in the Status display.
- Press button Y or E until 3 appears in the Service display.
- Press button S until 3 appears in the Status display.
- Current altitude shows in the Service display: 0 = low altitude, 1 = high altitude.
- Press Y/E or B/G until 1 (high altitude) appears, then press S to confirm. Repeat if 0 appears.
- Press S to exit setting mode.
- Press button R for more than 2 seconds to restart and apply settings.
- Fill out and apply the Altitude Conversion label next to the rating plate, and complete the conversion report.
Change gas type on burner control
Viessmann · Vitocrossal 200 CM2 burner control
Set the burner to natural gas or LPG. The burner must be in standby (Status 0, Service 0).
- Press button S and hold for more than 2 seconds until the display area flashes.
- Press button Y or E until 6 appears in the Service display.
- Press button S until 6 appears in the Status display.
- Press button Y or E until 2 appears in the Service display.
- Press button S until 2 appears in the Status display.
- Current gas type shows in the Service display: 0 = NG, 1 = LPG.
- Press Y/E or B/G to set 0 for NG or 1 for LPG.
- Press S to confirm. Repeat if 0 appears when 1 was expected.
- Press S to exit setting mode.
- Press button R for more than 2 seconds to restart and apply settings.
Check and reverse mixing valve motor rotation
Viessmann · Extension kit with mixing valve
The boiler runs a self-test at power-up in which the mixing valve opens and closes again. Use this with a manual test to confirm the motor direction. The motor direction is reversed by switching two core wires at a plug.
- Disconnect main power before opening the boiler.
- Watch the mixing valve during the self-test after switching on.
- Set the mixing valve manually to Open and check that the flow temperature sensor reads higher.
- To reverse the motor, remove the upper casing cover of the extension kit.
- At plug gS, switch the cores at terminals "|" and "~".
- Refit the casing cover and recheck operation.
Check fault messages without burner fault
Viessmann · Vitodens 100-W B1HE/B1KE
Use this to read a non-burner fault number so the contractor knows what to look for. The message facility turns back on the next day at 07:00 if troubleshooting is delayed.
- Tap OK to confirm.
- Press and hold the menu button for about 4 seconds, then tap OK.
- Select Error message, then tap OK to confirm.
- Select the required message, then tap OK to confirm.
- Write down the fault number shown, for example F.14.
- Use the back button to return a step, or select further messages.
- Select Contractor to view the heating contractor's contact details if entered.
- Hold the exit button for about 4 seconds to leave the menu.
Check flue gas temperature sensor and fixed high limit
Viessmann · Vitodens 100-W WB1B
Use the resistance curves to check the flue gas sensor. If the boiler cannot be reset after an F2 shutdown while water is below about 203°F (95°C), check the fixed high limit.
- Pull the leads from the flue gas temperature sensor and check its resistance against the curve; replace it if the deviation is severe.
- Pull the leads from the fixed high limit and check continuity with a multimeter.
- Replace the fixed high limit if it has no continuity.
- Coat the new fixed high limit with heat conducting paste and install it.
- Reset the control (see page 76).
Check maintenance messages
Viessmann · Vitocrossal 200 CI2 boilers
Maintenance messages show on the display when service intervals or limits are reached. The red indicator flashes in this case.
- Open the message lists from the main menu.
- Select "Service" to view the maintenance messages.
Check mixing valve motor direction
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0 with mixing valves
During an actuator test of a mixing valve the supply temperature must rise when the valve opens. If it falls, the motor is turning the wrong way or the valve set is fitted incorrectly.
- Run the mixing valve open test in the actuator test.
- Watch the supply temperature. It must rise as the valve opens.
- If the temperature drops, check the motor rotation and the valve set fitting against the mixing valve installation instructions.
Check operating data
Viessmann · Vitocrossal 200 CI2 service menu
Operating data is grouped in the diagnosis menu. Heating circuits with mixing valves only show data if those components are installed. A faulty sensor shows as dashes.
- Enter the service menu.
- Select Diagnosis.
- Select the required group, for example General.
Check sensor readings
Viessmann · Vitotronic 200-H
Each sensor is shown on the display with its own number. Scan the actual temperature of each one.
- Press the sensor scan button (symbol not legible in the source).
- Scroll through the sensors with the up or down arrow and read the actual temperature.
- Press OK to finish.
Check sensor temperatures
Viessmann · Vitotronic 200-H sensors
Puts the control in scanning mode to read actual sensor temperatures. See page 23 for scanning operating conditions.
- Press the scan key to start scanning operating conditions.
- Scroll through the actual temperatures with the arrow keys.
- Press the confirm key to finish scanning.
Check sensor temperatures in Diagnosis
Viessmann · Vitocrossal 300 CA3B
Scan the live temperature of a sensor from the service menu to check it against the actual reading.
- From the home screen, open Service and enter the 'viservice' password.
- Open Diagnosis.
- Select the sensor group.
- Scan the actual temperature of the sensor you are checking.
Check sensor temperatures on Vitotronic 300-K
Viessmann · Vitotronic 300-K, MW2B
Use the diagnosis menu to read the actual temperature of each sensor, grouped by sensor type.
- Press OK and the second menu key together for about 4 seconds.
- Select 'Diagnosis'.
- Select the sensor group (group list is on page 68 of the manual).
- Read the actual temperature of the sensor you need.
Check sensors (Vitocontrol-S)
Viessmann · Vitocontrol-S VD2/CT3/CM2
Scans actual temperatures in the operating-conditions scan mode.
- Press the button shown to start sensor scanning (scanning is active, see page 111).
- Scan the actual temperature with the up or down button.
- Press the button shown to finish. Scanning is completed.
Check sensors (Vitotronic 100)
Viessmann · Vitotronic 100 GC1
Scans the actual temperatures while the unit is in operating-conditions scan mode.
- Press the button shown to start sensor scanning (scanning is active, see page 106).
- Scan the actual temperature with the up or down button.
- Press the button shown to finish. Scanning is completed.
Check sensors and test relays
Viessmann · Vitotronic 200-H HK1B
Access the diagnosis and actuator test functions from the control.
- Press OK and hold together with the second button for about 4 seconds.
- To check sensors: select Diagnosis, then select the group (see page 31), then read the actual temperature of the sensor.
- To test relays: select Actuator test and switch the outputs as listed in the actuator test table.
Check service messages
Viessmann · Vitodens 100-W B1HE/B1KE
Read the service message number so the contractor can prepare before visiting. The contractor sets the service intervals, and Active messages appears when one is overdue.
- Tap OK to confirm.
- Select Active messages, then tap OK.
- Select Maintenance, then tap OK.
- Select the required message, then tap OK.
- Write down the service message number shown, for example P.1.
- Tap OK to confirm, then tell the contractor.
- Hold the exit button for about 4 seconds to leave the menu.
Check Vitotronic 200-H (LON connection)
Viessmann · Vitotronic 200-H accessory
The Vitotronic 200-H accessory connects to the control unit over LON. Test the link with a participant check on the boiler control unit.
- Disconnect main power before opening the boiler.
- Run the participant check at the boiler control unit (see page 37 of the manual).
Checking active maintenance messages
Viessmann · Vitodens 100-W
Shows any maintenance messages that are currently active.
- Use the selector to choose the active messages menu, then press OK.
- Select Maintenance and press OK.
- Existing messages are shown on the display.
Checking sensor temperatures
Viessmann · Vitotronic 300 GW6B
Reads the actual temperature of a sensor from the diagnosis menu.
- From the home screen tap Menu.
- Tap Service.
- Enter the viservice password.
- Tap Diagnosis.
- Select the group.
- Read the actual temperature of the required sensor.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.