Other: Water Heater tips (part 1 of 3)
Short, practical technician tips on other for water heater. Check each one against the manual for your exact model before acting.
Cascade pump may run with no hot water demand
Daikin · Cascade unit
The cascade pump can start even when hot water is not being supplied. This is anti-freeze protection and is normal.
Cold-weather shutdown: drain the cascade unit
Daikin · Mega-Q cascade unit
If the breaker is turned off while outdoor air is below freezing, water left in the cascade unit can freeze and damage the unit and piping.
- Drain the water from inside the cascade unit before shutting off the power circuit breaker in freezing conditions.
Do not use conventional refrigerant tools
Daikin · Mega-Q R410A circuit
Do not use gauge manifolds, charge hoses, gas leak detectors, reverse flow check valves, refrigerant charge bases, vacuum gauges or recovery equipment made for conventional refrigerants. Mixing conventional refrigerant or oil into R410A will degrade it.
- Use tools rated for R410A only.
- Keep the R410A circuit free of mineral oil, moisture and air.
Install the cascade unit on the left
Daikin · Mega-Q layout
Placing the cascade unit on the left of the heat source unit is recommended. Other layouts make refrigerant piping, water piping and wiring harder.
- Place the cascade unit on the left side of the heat source unit where possible.
Reading the subdivision code on the cascade unit
Daikin · Cascade unit
The subdivision code is not shown on the remote controller. Read it on the 7-segment display through the inspection port of the cascade unit electrical box cover.
- Remove the cascade unit electrical box cover inspection port cover.
- Read the subdivision code on the 7-segment display.
Sensor connection mismatch stops hot water supply
Daikin · Mega-Q hot water generation system, water temperature sensors
Sensor harness labels must match at both ends. A mismatch between the tank control board and the storage tank sensor connectors prevents hot water supply operation.
- Check the identification label on each relay harness connector.
- Check the matching identification label on each sensor device-side connector.
- Correct any mismatched connection before starting the unit.
Water is non-potable
Daikin · Mega-Q water circuit
Hot water made by Mega-Q is not drinking water. Scale build-up in the tank and piping wear can change water quality over time.
- Do not use the generated hot water for drinking.
- Use tap water that meets local water quality rules to protect condensers and piping.
- Install a strainer (60 mesh or finer) in the water piping.
2-way valve setting for internal or external pump
Navien · NPE-A2 and NHW700-A systems with internal or optional external pump
For the NPE-A2/NHW700-A system using the internal or an optional external pump, the 2-way valve inside the water heater is set to EXT.
- Set the 2-way valve inside the water heater to EXT.
Air intake location for ducting
Navien · NWP500-50, NWP500-65, NWP500-80
Outdoor air is often below 37°F (3°C) in fall and winter. Ducting outdoor air to the intake adds load to the heating and cooling system unless exhaust air is also directed outside. Keep the intake away from other appliance exhausts such as a dryer.
- Avoid drawing outdoor air unless exhaust is also ducted outside.
- Do not pull air from another indoor space without checking for negative pressure.
- Keep the intake away from dryer or other exhaust ducts.
Annual T&P valve flush
Navien · NWP500-50, NWP500-65, NWP500-80
Release water through the T&P valve once a year so it does not stick. Keep people clear, the water is very hot, and never block the discharge outlet.
- Turn off power to the water heater.
- Open the T&P valve handle on the side of the unit.
- Drain 1–2 gallons of water.
- Close the handle.
Clean the intake air filter
Navien · NWP500-50, NWP500-65, NWP500-80
Clean the air filter at the top intake duct once a year, or when the air filter alarm shows on the front panel. Replace it if required.
- Turn off power to the water heater.
- Hold the filter by its handle and pull it out of the intake air duct.
- Remove dust with water or a vacuum.
- If washed with water, dry it fully or wipe it dry.
- Push the filter all the way back into the intake duct.
Cold-weather power failure
Navien · Cold-climate installations with frequent outages
The freeze prevention system does not run without power, so the heat exchanger can freeze. In areas with frequent outages, drain the unit completely if power will be off for a long time. Freeze damage is not covered under warranty. A battery backup can supply hot water during outages.
- Drain the unit before any long power outage in cold areas.
Copper piping and dielectric unions
Navien · NWP500 series
Copper water lines can set up small galvanic currents that corrode connections. Dielectric unions are needed at the water connections.
- Install dielectric unions (field supplied) at the water connections when using copper piping.
- Use unions on the water lines so the heater can be removed later for service.
Delete a weekly operation schedule
Navien · NWP500-50, NWP500-65, NWP500-80
Removes one saved weekly schedule item.
- Press and hold Menu for more than 5 seconds, then select Schedule and Weekly List.
- Select the schedule item and press OK.
- Choose Yes and press OK to delete, or No to keep it.
Do not cut power during self diagnostic
Navien · NWP500 self diagnostic
Disconnecting power during the self diagnostic can damage the product. If power is cut and restored, the diagnostic restarts from the beginning.
- Do not disconnect power during the self diagnostic.
- If power was interrupted, allow the full self diagnostic to run again.
Electrical connection requirements
Navien · NWP500-50, NWP500-65, NWP500-80
Key wiring rules for the junction box and field connections.
- Open the circuit breaker or pull the fuses and confirm power is off with a non-contact tester before any electrical work.
- Follow the wiring diagram for all connections.
- Use 10 AWG solid copper wire for all connections.
- Secure wires with a UL-listed or CSA-approved strain relief.
- Connect the ground wire to the green ground screw.
- Replace the junction box cover and access doors after servicing.
Electrical connection safety for the junction box
Navien · NWP500-50, NWP500-65, NWP500-80
Contact with electrical parts in the junction box, behind access doors or inside the top shroud can cause fatal shock. Remove power at the breaker or fuses first and confirm it is off with a non-contact tester. Use 10 AWG solid copper, a UL-listed or CSA-approved strain relief, and a secure green ground screw. Replace the junction box cover and access doors after service.
- Open the circuit breaker or pull the fuses before any work.
- Confirm the power is off with a non-contact tester.
- Wire per the Wiring Diagram, using 10 AWG solid copper.
- Secure each cable with a UL-listed or CSA-approved strain relief.
- Connect the ground wire to the green ground screw.
- Refit the junction box cover and access doors.
Error indication on the remote
Navien · NR-21DU remote controller
When an error occurs, the LED turns red and blinks. This does not apply in Cascade mode, where the LED does not blink. The error code appears on the LCD display.
- If the LED is red and blinking, read the error code shown on the LCD.
- Look up the code in the error code guide of this manual.
Factory temperature setting and scald time table
Navien · NWP500-50, NWP500-65, NWP500-80
The factory setting is 120°F (49°C). Water at 125°F (52°C) or higher can cause instant scalds. Time to a serious burn drops quickly as temperature rises: 120°F takes more than 5 minutes, 125°F about 1.5 to 2 minutes, 130°F about 30 seconds, 140°F under 5 seconds, and 150°F about 1.5 seconds. Stack effect can make the tank water up to 30°F hotter than the set point, and a hot room or pre-heated inlet water can also raise it. The thermostat alone is not an accepted scald control under ASSE 1070, so a mixing or temperature-limiting valve may be needed above 125°F.
- Leave the setting at the lowest temperature that meets the user's needs.
- Use a lower setting where children, elderly or disabled users are present.
- Advise the user to feel the water before bathing.
- Install a thermostatic mixing valve or temperature-limiting valve if the setting must go above 125°F.
- Check local codes for maximum allowed temperatures in nursing homes, schools and day care centers.
Flooded appliance
Navien · All NPN models
Do not use the appliance if any part has been under water.
- Call a qualified service technician to inspect the appliance.
- Have the technician replace any part of the control system and any gas control that was under water.
Freeze protection and winter exposure
Navien · ComfortCirc recirculation pump
Insulate all exposed pipes in winter to prevent freeze damage. Do not unplug the pump or close valves during long winter absences, because the freeze prevention feature needs power and an open flow path. In extreme cold the pump runs automatically to protect the system.
- Insulate exposed piping before winter.
- Keep power on and valves open during extended winter absences.
Front panel and remote timer settings are disabled with the kit installed
Navien · NPN/NHW700 with HotButton Kit
With the HotButton Kit in place, the heater's own recirculation controls no longer apply.
- Do not expect remote controller timer settings to take effect; they are disabled.
- Do not expect front panel recirculation settings to take effect; they are disabled.
- Use the parameter P.12 to set recirculation pump run time.
Front panel buttons
Navien · NWP500 series
The front panel has five buttons for power, mode, menu navigation and temperature.
- Power button: turns the water heater on or off.
- Menu button: changes the operation mode and opens the menu screen.
- Up and Down buttons: raise or lower the temperature setting or a parameter, and move through menu items.
- OK button: selects the highlighted item.
- Back button: returns to the previous screen.
Front panel buttons and display icons (indoor models)
Navien · NPN indoor models
Indoor front panel buttons: Power, Up, Down, Reset, Information, Diagnostics (installers only), Hot Water Recirculation, Master Unit/Cascade. Display icons include Error (code shown), Combusting (burner on), Recirculation Mode and Cascade operation.
Front panel indicators
Navien · Indoor models with front panel
The front panel shows error codes, recirculation status, master or cascade status, and burner status.
- Error indicator: a code appears on the display when there is an error.
- Master Unit and Cascade operation indicators show multi-unit status.
- Hot Water Recirculation and Recirculation Mode indicators show recirculation status.
- Combusting indicator lights when the gas burner is on.
- Information button shows basic information.
Front panel status icons
Navien · NWP500-50, NWP500-65, NWP500-80
The display shows: schedule, error status, DR/Wi-Fi connection, operation mode, set temperature, anti-Legionella run (also shown in recirculation), recirculation status (Always On, Weekly, HotButton), heating element status (electric heater running, heat pump running, or heat pump stopped), hot water charge rate, and scald warning or freeze protection active.
- Use the error status icon to confirm a fault before reading the code.
- Check the heating element icons to see whether the electric heater or heat pump is running.
Gas line sizing and layout
Navien · CR and CC series water heaters
Use the water heater as the first appliance downstream of the meter.
- Install the water heater as the first appliance after the gas meter.
- Use the pipe sizing charts to select the gas supply pipe.
- Keep the gas connection at 3/4 in. minimum.
- Use flexible gas line only with adequate inner diameter and no crimps or tight bends.
- Install a manual gas shutoff valve close to the water heater.
- On rigid pipe, install a union close to the water heater.
Gas shut-off in case of damage
Navien · All NPN models
If the heater is damaged by overheating, fire, flood or another cause, shut off the gas.
- Close the manual gas shut-off valve if the heater is damaged or overheats.
- If the gas supply fails to shut off during overheating, close the manual gas valve to the appliance.
- Do not operate the heater again until a qualified technician has inspected it.
Get Technical Support pre-authorization before repairs
Navien · NWP500-50, NWP500-65, NWP500-80
All repairs on this water heater need pre-authorization from Navien Technical Support. The installer or a licensed professional should make that contact while standing at the unit.
- Have the installer or a licensed professional contact Navien Technical Support while at the installation site.
- Have the model number, serial number, date purchased, installation location and type ready.
- Give the error code shown on the front panel display, if one is showing.
- For water-side or electrical faults outside the water heater, have a licensed plumber or electrician check the affected system.
Handling and lifting the unit
Navien · NWP500-50, NWP500-65, NWP500-80
The unit is heavy and must be lifted with help.
- Lift the water heater with at least one assistant.
- Do not drop the unit while lifting or moving it.
- Shipping weight is 229 lb (NWP500-50), 265 lb (NWP500-65) or 282 lb (NWP500-80).
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.