Viessmann Heat Pump: Thermostat installation and third-party requirements
Thermostat installation and third-party requirements on a Viessmann heat pump: Mount the thermostat to block drafts. Third-party thermostats must support heat pump operation.
Applies to: Vitocal 100-WA terminal strip systems
How to fix thermostat installation and third-party requirements: step by step
- Mount the thermostat on foam tape to seal the wire penetration; silicone can also be used.
- Follow the thermostat instructions for programming in heat pump mode.
- Use two heat plus aux heat and two cool, 7-day programmable thermostat for third-party units.
- Wire Y2 for stage 2 heat or cool, B only on dual-speed systems, and E for strip heat if fitted.
- Leave E unwired if the system has no strip heat.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056
Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.