Viessmann Heat Pump: Refrigerant removal, evacuation and purging for flammable refrigerants
Refrigerant removal, evacuation and purging for flammable refrigerants on a Viessmann heat pump: Use this sequence before opening the refrigerant circuit for repair or any other purpose.
Applies to: Vitocal 100-AW AM2V refrigerant circuit
How to fix refrigerant removal, evacuation and purging for flammable refrigerants: step by step
- Remove the refrigerant safely following local and national rules.
- Evacuate the circuit.
- Purge with inert gas (optional for A2L).
- Evacuate again (optional for A2L).
- If flame is used to open the circuit, keep purging with inert gas throughout.
- Open the circuit.
- Purge with oxygen-free nitrogen, never compressed air or oxygen, and repeat as needed.
- Break the vacuum with nitrogen, fill to working pressure, vent to atmosphere, then pull vacuum again. Repeat until no refrigerant remains.
- Vent the system to atmospheric pressure before work starts.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.