Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Heat Pump: Refrigerant recovery for service or decommissioning

Updated · by Aurora Star Tech Inc.

Refrigerant recovery for service or decommissioning on a Viessmann heat pump: Recover flammable refrigerant safely into the correct equipment.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocal 100-WA R-454B refrigerant circuit

How to fix refrigerant recovery for service or decommissioning: step by step

  1. Take an oil and refrigerant sample before the task in case analysis is needed before reuse.
  2. Make sure electrical power is available before starting.
  3. Use only recovery cylinders designated and labelled for the recovered refrigerant, with a pressure-relief valve and shut-off valves in good order.
  4. Have enough cylinders for the total system charge.
  5. Evacuate and, if possible, cool empty recovery cylinders before recovery.
  6. Use recovery equipment in good working order, suitable for flammable refrigerant, with its instructions at hand.
  7. Have calibrated weighing scales available and in good working order.
  8. Use hoses with leak-free disconnect couplings in good condition.
  9. Process recovered refrigerant per local law and arrange the waste transfer note. Do not mix refrigerants.
  10. If compressors or oils are removed, evacuate them to an acceptable level first. Do not heat the compressor body with an open flame to speed this up.
  11. Drain oil safely.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Models

AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056

Source: Vitocal 100-WA Installation, Service and Operating Instructions, p. 57. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977