Viessmann Heat Pump: Refrigerant line set installation
Refrigerant line set installation on a Viessmann heat pump: Outdoor units ship with a full charge of R-454B. Charges, line sizing and capacities are based on 25 ft (7.6 m) runs; longer runs need a charge adjustment from the long line table. The outdoor unit uses an electronic expansion valve to control refrigerant flow to the indoor fan coil.
Applies to: All D5CSRA systems
How to fix refrigerant line set installation: step by step
- Do not bury the lines deeper than 36 in (914 mm).
- Give the lines at least a 6 in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
- Insulate both lines with at least 1/2 in (12.7 mm) insulation; closed-cell is recommended for long lines.
- Isolate the tubing from the building structure so vibration and noise do not transfer.
- For runs over 25 ft, add refrigerant per the long line table.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
More commissioning tips for heat pump
Source: Carrier D5CSRA Product Data, p. 188. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.