Viessmann Heat Pump: Pressure relief valve installation and discharge piping
Pressure relief valve installation and discharge piping on a Viessmann heat pump: The factory-supplied pressure relief valve must be used. No isolation valve may be placed between the heat pump and the relief valve. Air is removed through air vents on the system supply. Operating range is 8 psig (0.5 bar) minimum to 30 psig (2 bar) maximum.
Applies to: Indoor unit safety relief valve
How to fix pressure relief valve installation and discharge piping: step by step
- Install the supplied fittings and the 30 PSI relief valve on the supply-from-outdoor-unit connection of the indoor unit.
- Run the discharge pipe from the relief valve to a floor drain and end it about 6 in. (150 mm) above the drain.
- Keep the discharge end unthreaded and do not reduce the pipe diameter.
- Do not install a shutoff valve in the discharge pipe.
- Do not pipe the discharge to the outdoors.
- Orient the discharge pipe so it cannot scald people.
- Make sure supply and return lines have no restrictive piping that could trap air.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
Source: Vitocal 100-AW AM2V Technical Data Manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.