Viessmann Heat Pump: Open loop flow rate and water valve control

Updated · by Aurora Star Tech Inc.

Open loop flow rate and water valve control on a Viessmann heat pump: Flow is set by the modulating water valve. Size flow for open loop operation, and allow for higher flow if well water drops below 50°F (10°C) in the heating season.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Open loop systems

How to fix open loop flow rate and water valve control: step by step

  1. Set open loop flow to 2-3 GPM per ton (7.5-11.5 LPM per 3.5 kW).
  2. If groundwater may fall below 50°F (10°C) during heating season, calculate higher flow requirements.
  3. Use the water control valve at the unit outlet to keep pressure in the heat exchanger.
  4. Use either an ON/OFF two-position water valve or a proportional actuator with 2-10 VDC signal.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Models

AP1T 027020AP1T 040029AP1T 052038AP1T 066049AP1T 077056

Source: Vitocal 100-WA technical data manual, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.