Viessmann Heat Pump: Install pressure relief valve and discharge pipe
Install pressure relief valve and discharge pipe on a Viessmann heat pump: Install the factory safety valve on the supply from the outdoor unit and pipe its discharge safely to ground level.
Applies to: Outdoor unit AM2V 020028, 034043, 051078
Common causes of install pressure relief valve and discharge pipe
- Scalding risk to people if discharge is not directed to the ground.
- Air trapped in restrictive piping can stop the heat pump from purging.
How to fix install pressure relief valve and discharge pipe: step by step
- Use the supplied fittings to install the pressure relief valve on the supply from the outdoor unit.
- Fit the discharge pipe onto the relief valve so the pipe end is not threaded.
- Terminate the discharge pipe about 6 in (150 mm) above ground.
- Do not fit any shutoff valve in the discharge pipe.
- Keep the discharge pipe full diameter; do not reduce it.
- Do not install an isolation valve between the heat pump and the relief valve.
- Remove air through air vents in the system supply.
- Avoid restrictive piping in supply and return lines where air could be trapped.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
0200280340430510780340043AM2V 020028AM2V 034043AM2V 051078
Source: Vitocal 100-AW AM2V Technical Data Manual, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.