Viessmann Heat Pump: Hydronic installation requirements
Hydronic installation requirements on a Viessmann heat pump: The hydronic side must follow applicable standards and be sized for adequate flow. Flexible piping is needed to limit vibration. Heating medium piping must be insulated. A solids separator at the unit inlet is required for warranty.
Applies to: Vitocal 100-AW AM2V hydronic system
How to fix hydronic installation requirements: step by step
- Size the piping between outdoor and indoor units for adequate flow (see technical data table).
- Connect the heat pump to the system with flexible piping.
- Insulate all heating medium pipes and connections.
- Install a solids separator at the unit inlet.
- Keep the minimum heating medium pressure at 8 PSI (0.5 bar).
- Pipe so the indoor unit can run the heating circuit without the outdoor unit.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
More commissioning tips for heat pump
Source: Vitocal 100-AW AM2V installation, service and operating instructions, p. 46. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.